Technical Specifications
| Power supply | Rechargeable lithium-ion battery pack 9.6 V, backup charger. |
| Battery indicator | Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after 1 minute. |
| Power consumption | Current consumption of normal test 490 mA, continuous working for 8 hours. |
| Number of channels | 4 U or 4 I |
| Phase to phase voltage | 1.0 V to 2000 V |
| Phase-to-neutral voltage | 1.0 V to 1000 V |
| Current | 10 A current clamp: 10 mA to 10.0 A
100 A current clamp: 0.10 A to 100 A 1000 A current clamp: 1.0 A to 1000 A 6000 A Flexible Coil Current Sensor (with Integrator): 10 A to 6000 A |
| Frequency | 40 Hz to 70 Hz |
| Parameters of electricity | W, VA, Var, PF, DPF, cos φ, tan φ |
| Energy parameters | Wh, Varh, Vah |
| Harmonic | Order 0 to 50 |
| Total harmonic distortion | Order 0 to 50, each phase |
| Expert mode | Yes |
| Number of Transient records | 150 sets |
| Voltage flicker | Yes |
| Starting current mode | Yes, 100 sec |
| 3 phases unbalance | Yes |
| Record | 300 days (simultaneous recording 20 parameters, record one point every 5 seconds). |
| Min or Max recorded value | Measurement of maximum and minimum values over a period of time |
| Alarm | 40 different types of parameter selections, 12,800 sets alarm logs |
| Peak | Yes |
| Phasor diagram display | Automatically |
| Capacity of snapshots | 60 |
| Communication | USB |
| Automatic switching off | When an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off |
| Backlight function | Yes, suitable for use at night and in a dark place. |
| Input impedance | Input impedance of test voltage: 1 MΩ |
| Withstand voltage | Withstand 3700 V per 50 Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell |
| Insulation | Between instrument wiring and shell ≥ 10 M Ω |
| Structure | Double insulation, with insulation vibration proof sheath |
| Safely rules | IEC 61010 1000 V Cat III or 600 V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2 |
| Working temperature and humidity | 14 °F to 104 °F (-10 °C to 40 °C) below 80 % RH |
| Storage temperature and humidity | 14 °F to 140 °F (-10 °C to 60 °C) below 70 % RH |
| Display mode | LCD colour screen, 640 dots × 480 dots, 5.6 inches, display domain: 4.56 in x 3.46 in (116 mm × 88 mm) |
| Size of clamp | 10 A small sharp current clamp: 0.29 in x 0.51 in (7.5 mm × 13 mm)
100 A circle current clamp: 1.37 in x 1.57 in (35 mm × 40 mm); 1000 A circle current clamp: 2.67 in x 2.67 in (68 mm × 68 mm.) 6000 A Flexible Coil Current Sensor (with Integrator): 11.8 in (30 cm) |
| Instrument dimensions | 9.44 in x 6.69 in x 2.67 in (24 cm×17 cm× 6.8 cm) |
| Length of voltage test wire | 78.74 in (300 cm) |
| Length of current sensor wire | 118.11 in (200 cm) |
| Weight | Host: 3.53 lb (1.6 kg) (with battery)
10 A small sharp current clamp: 6 oz (170 g) × 4 100 A circle current clamp: 6.7 oz (190 g) × 4 1000 A circle current clamp: 17.99 oz (510 g) × 4 6000 A Flexible Coil Current Sensor (with Integrator): 11.64 oz (330 g) × 4 Test wires and power adapter: 31.75 oz (900 g) |
| Total Weight | 20.28 lb (9.2 kg) |