Overview
Hospitality Enviro Tech’s Industrial Earth Ground Resistance & Leakage Clamp Meter is fast and safe. This device measures indoor/outdoor earth-ground resistance and ac leakage currents without disconnecting the earth-ground stake from the grounding system. In addition, this clamp meter features a heavy-duty clamp jaw that stays in alignment and calibration in industrial conditions.
Features
- AC Leakage Current Measurement: Identify leakage without disconnecting the earth ground stake.
- Rugged Design: Heavy-duty clamp jaw maintains alignment and calibration in industrial environments.
- Data Logging: Automatically records and stores up to 32,760 measurements at pre-set intervals.
- Alarm Threshold: User-defined high/low limits for fast measurement evaluation.
- Band-Pass Filter: Selectable function for optimized measurements.
Technical Specification
| Specification | Details |
| Maximum Voltage to Earth Ground | 1000 V |
| Frequency Range | 40 Hz to 1 kHz |
| Ingress Protection | IEC/EN 60529: IP30 with jaw closed |
| LCD | Digital reading: 9999 counts, Refresh rate: 4/s |
| Overload Indication | OL |
| Display Reading Specification with Loop Resistance Standard | Input: 0.474 Ω, Minimum: 0.417, Maximum: 0.531
Input: 0.5 Ω, Minimum: 0.443, Maximum: 0.558 Input: 10 Ω, Minimum: 9.55, Maximum: 10.45 Input: 100 Ω, Minimum: 96, Maximum: 104 |
| Data Logging | Capacity: 32,760 measurements, Interval: 1 sec to 59 min 59 sec |
| Wireless Radio | Frequency range: 2412 to 2462 MHz, Output power: <10 mW, Radio frequency certification: FCC ID: T68-FBLE IC:6627A-FBLE |
| Safety | IEC/EN 61010-1: Pollution Degree 2, IEC/EN 61557-1IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 VIEC/EN 61557-13: Class 2, ≤30 A/mIEC/EN 61557-5, IEC/EN 61557-16: cutoff frequency 20 kHz (-3 dB) |
| Electromagnetic Compatibility (EMC) | IEC/EN 61326-1: Portable Electromagnetic Environment, CISPR 11: Group 1, Class BIEC/EN 61326-2-2, Korea (KCC): Class A equipmentUSA (FCC): 47 CFR 15 subpart B |
| Conductor Size | 1.57 inch (40 mm) approximately |
| Temperature | Operating: 14 to 122°F (-10 to 50°C)
Storage: -4 to 140°F (-20 to 60°C) Reference: 73°F ±9°F (23°C ±5°C) Coefficient: 0.15% X (specified accuracy)/°C |
| Operating Humidity | ≤90% RH at 50 to 86°F (10 to 30°C)
≤75% RH at 86 to 104°F (30 to 40°C) ≤45% RH at 104 to 122°F (40 to 50°C) (Non-condensing) |
| Altitude | Operating: 6561 ft (2000 m)
Storage: 39370 ft (12,000 m) |
| Battery | Type: 4 x 1.5 V AA alkaline, Life: More than 15 hrs (with backlight turned off, RF mode off) |
| Jaw Size | 1.37 in (35 mm) |
| Dimensions | 11.1 in x 4.1 in x 1.9 in (283 mm x 105 mm x 48 mm) |
| Weight | 31 oz (880 g) |








Reviews