Three-Channel AC Leakage Current Monitor with LCD Display – Hospitality Enviro Tech

Three channel AC leakage current monitor with LCD display, 200,000 data storage, and real-time monitoring for power system fault diagnosis. 

SKU: HETDCCM-201 Category:

Overview

Hospitality Enviro Tech Three-Channel AC Leakage Current Monitor with LCD Display is designed and manufactured for on-site simultaneous monitoring and recording 1 to 3 channel AC current or leakage current, it is composed of recorder host, current clamps, charger, monitoring software and communication cable, etc. Widely used in 380/220 v power system, provide safe, accurate and convenient power instrument for power inspectors. Host adopts LCD display, three channels with the same screen display, clear at a glance, there are Chinese and English operation interface two choices, suitable for different countries of engineering and technical personnel. The recorder is equipped with a large capacity rechargeable lithium battery, displays power energy with a three-grid mode, which can continue recording for up to 7 days. With the function of system clock and super storage space, it can set the monitoring and recording time on site, can store 200,000 sets of data, and has the function of setting the interval time of automatic storage, setting from 1 to 99 minutes. Monitoring software has online real-time monitoring and historical query functions, historical data reading, consulting, saving, reporting and other functions. The current clamp is made of Permalloy and adopts CT technology and unique double layer magnetic shielding technology. It is almost unaffected by the external magnetic field, which ensures uninterrupted monitoring for a long time with high accuracy, stability and reliability. 

 

Technical Specifications

Functions online monitoring and recording 1 to 3 channel AC leakage current and current, used for circuit insulation fault troubleshooting, monitoring intermittent leakage fault, check the happen time of insulation fault and maintenance lines, etc.
Power Source DC 3.7 V rechargeable lithium battery (full charge about 4.2 V)
Testing Method Clamp CT, TRMS
Display Mode LCD 128 dots × 64 dots
Current Clamp 1 to 3 PCS (Optional)
Current Clamp Lead Cable 2 core shield wire, length 78.7 in (2 M)
Sampling Rate 2 times/second
Data Storage 200,000 groups (Power down or replace battery will not lose the data)
Record Period Set the record interval time within 1 second to 99 minutes, 0 seconds is not automatically stored.
Record Time 1. Interval time 1 seconds, can continues recording 48 hours
2. Interval time 10 seconds, can continues recording 120 hours
3. Interval time 1 minute, can continues recording 168 hours
Download Speed 60 KB/ Min
Line Voltage Below AC 600 V circuit test
Overflow Display Exceed measure range overflow function: “OL” symbol display
Battery Voltage Use 3.7 V rechargeable lithium battery, power energy display with 3 grids, when the power energy is 0-grid indicate battery voltage is low, please charge in time
Rated Power In power save mode about 6 mA, Max about 35 mA
Communication Interface USB
Record Time In power save mode continues working 7days
Insulation Resistance 100 MΩ or larger, 1000 V
Accessories Host, Current Clamps 1-3 pcs Optional, USB/Charge Cable 1, Software CD 1, Handbag 1, Charger 1, User Manual
Working Temperature Working: 14 ℉ to 104 ℉ (-10 ℃ to 40 ℃); below 80% rh
Stored Temperature Storage: 14 ℉ to 140 ℉ (-10 ℃ to 60 ℃); below 70% rh
LCD Dimension Display field: 1.73 in × 1.06 in (44 mm × 27 mm)
Instrument Dimension Host: 3.07 in × 6.49 in × 1.65 in (78 mm × 165 mm × 42 mm); Current clamp 030: 4.52 in × 2.75 in × 1.29 in (115
mm × 70 mm × 33 mm)
Weight Host: 0.72 lb (0.33 Kg); Current clamp 030: 0.37 lb (0.17 Kg)